Environmental Specifications
Specification |
Value |
||
---|---|---|---|
Operating Temperature |
–40º C to 65º C
|
||
Nonoperational temperature |
40 to 158°F (-40 to 70°C) |
||
Non-operational temperature (Transportation or Storage, or both) |
-40°F (-40°C) for 72 hrs 158°F (70°C) for 72 hrs Section 4.1.1.1 of GR-63 or Section 9.1 of ATIS-0600010.2007 104°F (40°C) and 95% RH for 96 hrs Section 4.1.1.3 of GR-63 or Section 9.3 of ATIS-0600010.2007 |
||
Operational humidity |
5% to 95%, RH condensing (GR-3108, Class 3) |
||
Non-operational humidity |
5% to 95% RH |
||
Non-operational altitude |
15000 ft |
||
Operational mechanical shock |
Acceleration half sine 50 m/s^2, for 11msec. 100 shocks/surface (EN 300 019-2-4 V2.3.1) |
||
Non-operational mechanical shock |
Acceleration half sine 180 m/s^2, for 6msec. 100 shocks/surface. (EN 300 019-2-2 V2.3.1) |
||
Operational vibration |
2.5-200 Hz with spectral break point of 0.1 [(m/s²)²]/Hz (0.001 g²/Hz) at 2.5 - 5 Hz 6 db/octave and 100-200 Hz at -24 db/octave. (EN 300 019-2-4 V2.3.1) |
||
Non-operational vibration |
5-200 Hz with spectral break point of 1.0 [(m/s²)²]/Hz (0.01 g²/Hz) at 5 - 100 Hz -6 db/octave and 20-200 Hz at -24 db/octave. (EN 300 019-2-2 V2.3.1) |
||
Cold start |
-40°F (-40°C) |
||
Hot start |
149°F (65° C) |
||
Non-operational Free-Fall Drop |
Drop the unpackaged sample 3.9" onto a rigid surface. Drop 1 face, 2 edges, and 2 corners. (ENG-339611.Rev2 [Test Method: IEC-68-2-32]) |
||
Earthquake, Zone 4 |
Equipment complies with earthquake tests per sections 4.4.1 and 5.4.1 of GR-63 or ANSI TI-329 (GR-3108 Class 3) |