Migrating to a Back-to-Back System

The Universal Fabric Card (UFC) supports a back-to-back configuration between two Cisco NCS 6000 LCCs. The back-to-back configuration is supported on Cisco IOS XR release 6.2.1 and later releases. This chapter describes how to migrate two Cisco NCS 6000 LCC routers from single-chassis to a back-to-back configuration.

Prerequisites

  • Before you perform any procedures, review the safety guidelines in the Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide to avoid injuring yourself or damaging the equipment.

  • Before cabling the system, install each line card chassis (LCC) in the planned location. Ensure that you have adequate floor space to cable the back-to-back configuration and an environment that meets the recommended specifications. For more information, see the Cisco Network Convergence System 6000 Series Routers Site Planning Guide.

  • Verify that both single chassis routers (RACK0 and RACK1) are running Cisco IOS XR release 6.2.1 or later (with all applicable SMUs and packages).

  • From each chassis, use the show chassis command from SysAdmin VM and make note of each chassis serial number.


    Note

    The chassis serial number can also be found on the label on the chassis front/rear face plate.
  • Perform the Router Health check on both routers to ensure that any errors or exception are resolved prior to migrating to back-to-back mode. See Commands for Router Health Check.

  • Verify that field-programmable device (FPD) upgrades are completed for all FPDs on both routers by using the show hw-module fpd command. For any FPD components that show status as NEED UPGD, use the upgrade hw-module location location fpd command. For any FPD components that show status as RLOAD REQ, use the hw-module location location reload command.

  • Create a backup of the RACK0 running configuration using the copy running-config command in both System Admin EXEC mode and XR EXEC mode.

Required Tools and Equipment

For a fully-loaded back-to-back configuration, the following Cisco NCS 6000 hardware is required:

  • 2 Cisco NCS 6000 routers (NCS-6008)

  • 4 Fan Trays (NC6-FANTRAY or NC6-FANTRAY-2)


    Caution

    Both fan trays installed in a chassis must be the same type. Do not install NC6-FANTRAY and NC6-FANTRAY-2 fan trays in the chassis.
  • 4 Power Trays, with 6 PEM for each Power Tray (NCS-AC-PWRTRAY)

  • 4 Route Processors (NC6-RP)

    For the Route Processor Ethernet Control connections between RACK0 and RACK1:

    • 8 SFP+ optics (SFP-10G-SR)

    • 4 LC-to-LC OM3 Multimode cables

  • 12 Universal Fabric Cards (NC6-FC2-U)

    For the Fabric Card connections between RACK0 and RACK1:

    • 2 optical module set that includes 96 CXP-100G-SR12 modules each (NCS-FAB-OPT)

    • 96 MTP-24 100G Multimode cables


      Note

      Install a CXP transceiver module or an EMI/dust plug (supplied) in all CXP ports. Do not operate the FC with an open port.
  • Supported line cards:

    • NC6-10X100G-M-P—10-port 100Gbps CXP

    • NC6-10X100G-L-P—10-port 100Gbps CXP

    • NC6-10X100G-M-K—10-port 100Gbps CPAK

    • NC6-2/10X100G-L-K—10-port 100Gbps CPAK

    • NC6-60X10GE-L-S—60-port 10Gbps SFP+

    • NC6-60X10GE-M-S—60-port 10Gbps SFP+


    Note

    The 20-port 100Gbps Line Card (NC6-20X100GE-L-C, NC6-20X100GE-M-C) is not supported in back-to-back configuration.

Additional required tool and equipment:

  • ESD (Electrostatic Discharge) wrist strap (for inserting a optical modules)

  • Number-2 Phillips screwdriver

  • Cable Director (P/N 2123610-1), to provide support and strain relief for fabric cable connections (provided by Cisco approved vendor Tyco Electronics)

  • Supply of Velcro tie wraps (to bundle cables)

  • Ladder

Migrating RACK0 Fabric Planes to Back-to-Back Mode


Note

This procedure must be completed for each fabric plane, one at a time, on RACK0.

To migrate to back-to-back mode using the Universal Fabric Cards (UFC), perform the following steps on RACK0:

Before you begin

Review and perform all tasks in the safety guidelines, prerequisites, and required equipment sections before performing this task.

Procedure


Step 1

From SysAdmin VM configuration mode, shut down the fabric plane.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# controller fabric plane 0 shutdown
sysadmin-vm:0_RP0(config)# commit
sysadmin-vm:0_RP0(config)# exit

Step 2

Use the show controller fabric plane all detail command to verify that the fabric plane Admin State and Plane State are down.

Example:


sysadmin-vm:0_RP0# show controller fabric plane all detail

Plane Admin Plane  Plane  up->dn  up->mcast Total   Down    PPU
Id    State State  Mode   counter   counter Bundles Bundles State
-----------------------------------------------------------------
0     DN    DN     SC           0          0     16       0    NA
1     UP    UP     SC           0          0     16       0    NA 
2     UP    UP     SC           0          0     16       0    NA
3     UP    UP     SC           0          0     16       0    NA 
4     UP    UP     SC           0          0     16       0    NA
5     UP    UP     SC           0          0     16       0    NA

Step 3

From SysAdmin VM configuration mode, power off the fabric card.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# hw-module shutdown location 0/FC0
sysadmin-vm:0_RP0(config)# commit
sysadmin-vm:0_RP0(config)# exit

Step 4

Use the show platform location command to verify that the fabric card is powered off.

Example:


sysadmin-vm:0_RP0# # show platform location 0/FC0
Mon Dec  5  23:54:02.366 UTC
Location  Card Type              HW State      SW State         Config State
----------------------------------------------------------------------------
0/FC0     NC6-FC                 POWERED_OFF   N/A              NSHUT

Step 5

Remove the legacy fabric card following the steps in the Removing a Fabric Card section.

Step 6

Install the UFC following the steps in the Installing a Fabric Card section.

Note 
Do not connect any cables to the UFC.
Step 7

From SysAdmin VM configuration mode, change the fabric plane mode to B2B.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# controller fabric plane 0 b2b
sysadmin-vm:0_RP0(config)# commit
sysadmin-vm:0_RP0(config)# exit

Step 8

Use the show controller fabric plane all detail command to verify that the fabric plane mode is B2B and that Admin State and Oper State are down.

Example:


sysadmin-vm:0_RP0# show controller fabric plane all detail

Plane Admin Plane  Plane  up->dn  up->mcast Total   Down    PPU
Id    State State  Mode   counter   counter Bundles Bundles State
-----------------------------------------------------------------
0     DN    DN     B2B          0          0     16       0    NA
1     UP    UP     SC           0          0     16       0    NA 
2     UP    UP     SC           0          0     16       0    NA
3     UP    UP     SC           0          0     16       0    NA 
4     UP    UP     SC           0          0     16       0    NA
5     UP    UP     SC           0          0     16       0    NA

Step 9

From SysAdmin VM configuration mode, unshut the fabric card.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# no hw-module shutdown location 0/FC0

0/RP0/ADMIN0:Dec  5 11:27:52.757 : shelf_mgr[2921]: %INFRA-SHELF_MGR-6-CARD_HW_OPERATIONAL :
 Card: 0/FC0 hardware state going to Operational
0/RP0/ADMIN0:Dec  5 11:28:09.532 : confd_helper[2900]: %MGBL-CONFD_HELPER-5-SYSADMIN_COMMIT :
 A sysadmin configuration change has been committed. Use 'show configuration commit list'
 in admin mode for more details
LC/0/0/CPU0:Dec  5 11:28:15.538 : fia_driver[246]: %PLATFORM-CIH-5-ASIC_ERROR_THRESHOLD : fia[2]:
 A link-err error has occurred. CMIC.CMIC_CMC0_IRQ_STAT3.RTP.Interrupt_Register.LinkMaskChange 
 Threshold has been exceeded
LC/0/5/CPU0:Dec  5 11:28:15.740 : fia_driver[216]: %PLATFORM-CIH-5-ASIC_ERROR_THRESHOLD : fia[4]:
 A link-err error has occurred. CMIC.CMIC_CMC0_IRQ_STAT3.RTP.Interrupt_Register.LinkMaskChange 
 Threshold has been exceeded
LC/0/2/CPU0:Dec  5 11:28:15.927 : fia_driver[293]: %PLATFORM-CIH-5-ASIC_ERROR_THRESHOLD : fia[3]:
 A link-err error has occurred. CMIC.CMIC_CMC0_IRQ_STAT3.RTP.Interrupt_Register.LinkMaskChange 
 Threshold has been exceeded
0/RP0/ADMIN0:Dec  5 11:28:17.401 : fsdbagg[4620]: %FABRIC-FSDB_AGG-5-PLANE_UPDOWN : [4620] :
 Plane 0 state changed to UP

sysadmin-vm:0_RP0(config)# commit
sysadmin-vm:0_RP0(config)# exit

Step 10

Use the show platform location command to verify that the fabric card is operational.

Example:


sysadmin-vm:0_RP0# show platform location 0/FC0
Mon Dec  5  23:54:02.366 UTC
Location  Card Type              HW State      SW State         Config State
----------------------------------------------------------------------------
0/FC0     NC6-FC2-U              OPERATIONAL   N/A              NSHUT

Step 11

Use the show hw-module fpd command to verify the status of all FPDs.

Verify that no FPD components require an upgrade (as indicated by NEED UPGD in the Status field) and that the Running and Programmed fields display the same version. See the Prerequisites section for FPD upgrade information.
Step 12

From SysAdmin VM configuration mode, unshut the fabric plane.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# no controller fabric plane 0 shutdown
sysadmin-vm:0_RP0(config)# commit
sysadmin-vm:0_RP0(config)# exit

Step 13

Use the show controller fabric plane all detail command to verify that the Plane Mode is B2B and that Admin State and Plane State are up.

Example:


sysadmin-vm:0_RP0# show controller fabric plane all detail

Plane Admin Plane  Plane  up->dn  up->mcast Total   Down    PPU
Id    State State  Mode   counter   counter Bundles Bundles State
-----------------------------------------------------------------
0     UP    UP     B2B          0          0     16       0    NA
1     UP    UP     SC           0          0     16       0    NA 
2     UP    UP     SC           0          0     16       0    NA
3     UP    UP     SC           0          0     16       0    NA 
4     UP    UP     SC           0          0     16       0    NA
5     UP    UP     SC           0          0     16       0    NA

Step 14

Perform the Router Health Check. See Commands for Router Health Check.


What to do next

Repeat these steps for each remaining fabric plane (FC1, FC2, FC3, FC4, and FC5) until all six fabric planes have been migrated to back-to-back mode.

Go to the next section to add RACK1 to back-to-back mode.

Adding RACK1 to Back-to-Back Mode

To add RACK1 to back-to-back mode, perform the following steps:

Before you begin

Review and perform all tasks in the safety guidelines, prerequisites, and required equipment sections before performing this task.

Use the show chassis command and make note of serial number for the chassis.

Perform all steps in the Migrating RACK0 Fabric Planes to Back-to-Back Mode for each fabric plane on RACK0.

Procedure


Step 1

Power off RACK1.

Step 2

Remove all line cards following the steps in the Removing a Line Card section.

Step 3

Remove all legacy fabric cards following the steps in the Removing a Fabric Card section.

Step 4

Install the Universal Fabric Cards (UFCs) following the steps in the Installing a Fabric Card section.

Step 5

Power on RACK1.

Step 6

Use the show hw-module fpd command to verify the status of all FPDs.

Verify that no FPD components require an upgrade (as indicated by NEED UPGD in the Status field) and that the Running and Programmed fields display the same version. See the Prerequisites section for FPD upgrade information.
Step 7

Power off RACK1.

Step 8

From SysAdmin VM configuration mode on RACK0, configure the chassis serial numbers.

Example:


sysadmin-vm:0_RP0# config
sysadmin-vm:0_RP0(config)# chassis serial NNN######NA
sysadmin-vm:0_RP0(config)# rack 0
sysadmin-vm:0_RP0(config)# chassis serial NNN######NB
sysadmin-vm:0_RP0(config)# rack 1
sysadmin-vm:0_RP0(config)# commit

Step 9

Connect the Ethernet Control between RACK0 and RACK1.

See the Cabling the Ethernet Control Plane section.

Step 10

Connect the Fabric between RACK0 and RACK1.

See the Cabling the Fabric section.

Step 11

When all Ethernet Control and Fabric connections have been made, power on RACK1.

Step 12

Use the show platform command to verify that the fabric card is operational.

Example:


sysadmin-vm:0_RP0# show platform
Mon Dec  6  00:54:02.366 UTC
Location  Card Type               HW State      SW State      Config State
---------------------------------------------------------------------------
0/FC0     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/FC1     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/FC2     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/FC3     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/FC4     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/FC5     NC6-FC                  OPERATIONAL   OPERATIONAL   NSHUT
0/3       NC6-10X100G-M           OPERATIONAL   OPERATIONAL   NSHUT
. . .

Step 13

Perform the Router Health Check. See Commands for Router Health Check.

Step 14

Install the line cards following the steps in the Installing a Line Card section.


Both RACK0 and RACK1 are in back-to-back mode.

Cabling Overview

Cable Routing Considerations

Cabling Routing

Whether the cables will be run overhead or under the floor, consider the airflow and cable characteristics of the combined cable sets to ensure that your cable management structures support the total capacity of cables for the Cisco NCS 6000 back-to-back system installation.

Raised Floor Installations

To plan cable routing in an installation with a raised floor, consider all the characteristics of each cable required for the installation. Allow slack for cabling so that cables can be pooled under the floor for future expansion without exceeding bend radius or cable length limitations. Riser cables are not rated for installation in air plenum passages, nor are they designed for use in LSZH (low smoke zero halogen) applications.

Cable Characteristics

Plan your cable runs, consider the characteristics of each cable, such as the cable length limitations, combined diameter of bundled cables (such as power cables), weight of the cable groups, and bend radius of the cable or cables. Couple these considerations with the cable infrastructure available (or needed) at your facility. The infrastructure could include structures like the overhead cabling monorail or J-hook system, sleeve and riser diameters, and distances between floors or elements of the Cisco NCS 6000 back-to-back system.

Analyze the cabling infrastructures, risers, and racking available in your facility to determine if the capacity of the cabling management systems at your facility will accommodate the required capacities of the back-to-back system cabling.

Cable Length

The limit of the cables is 100 meters (328 feet). Consider this distance when planning the physical locations of the LCCs. For more information on the range of lengths available for the OM4 fabric cables, contact a Cisco approved vendor such as Tyco Electronics or Molex.

Cable Bend Radius

Exceeding the bend radius allowed for a cable can break the glass in the cable or cause attenuation or loss of signal. Do not bend a cable more than the allowable bend radius.

See the Cisco Network Convergence System 6000 Series Routers Site Planning Guide for information on planning component locations and cable runs.

General Cabling Procedures

Observe these procedures as you attach every cable:

  • Strap the bundles to the horizontal cable management brackets on the chassis.

    Four horizontal cable management brackets are preinstalled on the LCC (two on the front side and two on the rear side of each chassis).

  • Handle all fiber-optic cables carefully.

    • Do not allow a fiber-optic cable to bend in a radius smaller than the allowable bend radius specified for that cable type.

    • Fiber-optic cables are glass. Do not step on fiber-optic cables or handle them roughly. Do not twist or stretch the cables.

    • To keep optical connections clean, do not remove the cable dust cover until immediately before you install the cable.

    • After you install a cable, immediately reserve each dust cover for storage by office personnel in a dust-free storage area. After all of the cables have been installed ensure that all the reserved dust covers are stored by office personnel in a dust free area for future use.

    • Install clean dust covers on every unused connection.

    • Consider labeling the chassis interconnection cables or creating a diagram of the cabling to ensure that the cables are connected correctly during system installation.

    • Consider labeling the chassis. Consider whether each chassis need to be physically positioned in sequence. Label each cable with the location of each termination as you install each cable

MPO-24 Cable Specifications


Note

Cisco provides the optical modules but does not provide the cables. You can order these cables from a Cisco approved vendor such as Tyco Electronics or Molex. To obtain the optics, please contact your Cisco sales representative for further information.

Note

The CXP pluggable transceiver module has 12 dedicated transmit (Tx) channels and 12 receive (Rx) channels per transceiver with data rates up to 10.3125 Gbps and OTN rates up to 11.25 Gbps. The CXP module provides 2-wire serial (I2C) management interface and digital diagnostics, including Tx and Rx optical power monitoring per wavelength. The CXP module uses a 24-fiber MPO connector that supports bidirectional transmission across the fibers (12 Tx + 12 Rx).

Note

Install a CXP transceiver module or an EMI/dust plug (supplied) in all CXP ports. Do not operate the fabric card with an open port.

The following figure shows the MPO-24 connector pinouts.

Figure 1. MPO-24 Connector Pinouts

The following figure shows the MPO-24 connector fiber assignments.

Figure 2. MPO-24 Connector Fiber Assignments

The following table lists the 100G to 100G crossover cable connections.

Table 1. Crossover Cable Connections

MPO Connector

CXP Module

Connector

CXP Module

Connector ID

Fiber ID

Pin

Transmit (TX) Receive (RX)

Connector ID

Fiber ID

Pin

Transmit (TX) Receive (RX)

MPO1

F1

1

RX

MPO1

F13

1

RX

MPO2

F2

2

RX

MPO2

F14

2

RX

MPO3

F3

3

RX

MPO3

F15

3

RX

MPO4

F4

4

RX

MPO4

F16

4

RX

MPO5

F5

5

RX

MPO5

F17

5

RX

MPO6

F6

6

RX

MPO6

F18

6

RX

MPO7

F7

7

RX

MPO7

F19

7

RX

MPO8

F8

8

RX

MPO8

F20

8

RX

MPO9

F9

9

RX

MPO9

F21

9

RX

MPO10

F10

10

RX

MPO10

F22

10

RX

MPO11

F11

11

RX

MPO11

F23

11

RX

MPO12

F12

12

RX

MPO12

F24

12

RX

MPO13

F13

13

TX

MPO13

F1

13

TX

MPO14

F14

14

TX

MPO14

F2

14

TX

MPO15

F15

15

TX

MPO15

F3

15

TX

MPO16

F16

16

TX

MPO16

F4

16

TX

MPO17

F17

17

TX

MPO17

F5

17

TX

MPO18

F18

18

TX

MPO18

F6

18

TX

MPO19

F19

19

TX

MPO19

F7

19

TX

MPO20

F20

20

TX

MPO20

F8

20

TX

MPO21

F21

21

TX

MPO21

F9

21

TX

MPO22

F22

22

TX

MPO22

F10

22

TX

MPO23

F23

23

TX

MPO23

F11

23

TX

MPO24

F24

24

TX

MPO24

F12

24

TX

Cabling the Ethernet Control Plane

This section describes how to cable the Ethernet control plane between the RACK0 and RACK1 in mesh configuration to ensure Ethernet control plane failover connectivity across both racks. The Ethernet control plane carries all the signaling, routing updates, system configuration, and management packets for the NCS 6000.


Note

See the Required Tools and Equipment section for more information on the required equipment.

The following figure shows the Ethernet control plane connections.

Figure 3. Cabling the Ethernet Control Plane in Back-to-Back Mode
Table 2. Ethernet Control Plane Cabling for Back-to-Back Mode

RACK0

RACK1

RP0, EXP0

RP0, EXP0

RP0, EXP1

RP1, EXP0

RP1, EXP0

RP0, EXP1

RP1, EXP1

RP1, EXP1

Cabling the Fabric

This section describes how to cable the UFCs between RACK0 and RACK1 for back-to-back mode.


Note

See the Required Tools and Equipment section for more information on the required equipment.

The fabric provides the data connection for router traffic between all the CXP optical ports in the line card chassis. The fabric cabling must be completed to enable data communications.

The following figure shows the fabric connections for one fabric plane. To complete the configuration, you must repeat the cabling for the remaining five fabric planes until all fabric cards are connected.

Figure 4. Cabling Fabric Plane 0 in Back-to-Back Mode
Table 3. Cabling the Fabric for Back-to-Back Mode

Plane 0

Plane 1

< . . . >

Plane 5

RACK0 slot/port to RACK1 slot/port

0/FC0/0 to 1/FC0/0

0/FC1/0 to 1/FC1/0

< . . . >

0/FC5/0 to 1/FC5/0

0/FC0/1 to 1/FC0/1

0/FC1/1 to 1/FC1/1

< . . . >

0/FC5/1 to 1/FC5/1

0/FC0/2 to 1/FC0/2

0/FC1/2 to 1/FC1/2

< . . . >

0/FC5/2 to 1/FC5/2

0/FC0/3 to 1/FC0/3

0/FC1/3 to 1/FC1/3

< . . . >

0/FC5/3 to 1/FC5/3

0/FC0/4 to 1/FC0/4

0/FC1/4 to 1/FC1/4

< . . . >

0/FC5/4 to 1/FC5/4

0/FC0/5 to 1/FC0/5

0/FC1/5 to 1/FC1/5

< . . . >

0/FC5/5 to 1/FC5/5

0/FC0/6 to 1/FC0/6

0/FC1/6 to 1/FC1/6

< . . . >

0/FC5/6 to 1/FC5/6

0/FC0/7 to 1/FC0/7

0/FC1/7 to 1/FC1/7

< . . . >

0/FC5/7 to 1/FC5/7

0/FC0/8 to 1/FC0/8

0/FC1/8 to 1/FC1/8

< . . . >

0/FC5/8 to 1/FC5/8

0/FC0/9 to 1/FC0/9

0/FC1/9 to 1/FC1/9

< . . . >

0/FC5/9 to 1/FC5/9

0/FC0/10 to 1/FC0/10

0/FC1/10 to 1/FC1/10

< . . . >

0/FC5/10 to 1/FC5/10

0/FC0/11 to 1/FC0/11

0/FC1/11 to 1/FC1/11

< . . . >

0/FC5/11 to 1/FC5/11

0/FC0/12 to 1/FC0/12

0/FC1/12 to 1/FC1/12

< . . . >

0/FC5/12 to 1/FC5/12

0/FC0/13 to 1/FC0/13

0/FC1/13 to 1/FC1/13

< . . . >

0/FC5/13 to 1/FC5/13

0/FC0/14 to 1/FC0/14

0/FC1/14 to 1/FC1/14

< . . . >

0/FC5/14 to 1/FC5/14

0/FC0/15 to 1/FC0/15

0/FC1/15 to 1/FC1/15

< . . . >

0/FC5/15 to 1/FC5/15