Introduction
This document describes common methods to troubleshoot power supplies on Catalyst 9000 Series Switches.
Prerequisites
Requirements
Cisco recommends that you have knowledge of these topics:
- Catalyst 9000 Series Switches architecture.
Components Used
The information in this document is based on these software and hardware versions:
The information in this document was created from the devices in a specific lab environment. All of the devices used in this document started with a cleared (default) configuration. If your network is live, ensure that you understand the potential impact of any command.
Physical Troubleshooting
- Verify what color on the PS LED is displayed (green/amber/red/off).
LED status
|
Signification
|
Off
|
No AC power is present in any power supplies.
|
Green
|
This power supply operates properly in main power mode.
|
Solid Amber
|
Indicates one of the following:
-
No output power available
-
AC/DC input is under the range of operation
-
Over voltage/over current/over temperature conditions
-
Over-temperature protection (OTP) due to fan failure
|
Blinking Amber
|
Indicates warning events such as a power supply module that continues to operate in high temperature or high power and a fan that runs slow and so on.
|
Red
|
Power supply failure.
|
Note: Consult specific hardware installation guide for each platform, meaning of LED color can vary from platform to platform.
2. If LED color is other than green, try the next tests:
Test
|
Steps
|
Reset the power supply
|
- Remove the PS from it slot.
- Wait a couple of minutes.
- Re-insert the PS to its slot.
|
Reset the power cord
|
- Remove the power cord from the affected PS.
- Wait a couple of minutes.
- Re-insert the power cord back to the PS.
|
Swap components
|
- Try to use a
well-known working power cord.
- Try to use a
well-Known working power outlet.
- Try a spare power supply on the same slot.
- Try the same faulty PS in a
well-known working slot.
- Try the same faulty PS in a different switch.
|
Note: If applicable, ensure there are no cable tie or any other object that can block the PS fan.
Common Verification Commands
Command
|
How to use
|
Switch#show inventory
|
Verify power supply is detected in the inventory.
|
Switch#show post
|
Verify all the tests are in passed status.
|
Switch#show log
|
Look for any error message related with with the issue.
|
Catalyst 9300
Verification Commands
Use show environment power
privilege EXEC command to verify PS status and budget.
Switch#show env power
SW PID Serial# Status Sys Pwr PoE Pwr Watts
-- ------------------ ---------- --------------- ------- ------- -----
2A PWR-C1-1100WAC <snip> OK Good Good 1100
2B Not Present
Use show power inline
privilege EXEC command to verify power budget available for PoE is properly allocated base on the power supplies installed.
Switch#show power inline
Module Available Used Remaining
(Watts) (Watts) (Watts)
------ --------- -------- ---------
2 595.0 0.0 595.0
Use show stack-power detail
privilege EXEC command (applies only to devices configured as stack power) to verify stack power mode, power allocation, stack power ports status and so on.
Switch#show stack-power detail
Power Stack Stack Stack Total Rsvd Alloc Sw_Avail Num Num
Name Mode Topolgy Pwr(W) Pwr(W) Pwr(W) Pwr(W) SW PS
-------------------- ------ ------- ------ ------ ------ ------ ----- -----
power-stack-1 SP-PS Ring 6600 30 1695 4875 3 6
power-stack-1-1 SP-PS Ring 4400 30 1193 3177 2 4
Power stack name: power-stack-1
Stack mode: Power sharing
Stack topology: Ring
Switch 4:
Power budget: 2043
Power allocated: 434
Low port priority value: 22
High port priority value: 13
Switch priority value: 4
Port 1 status: Connected
Port 2 status: Shut
Neighbor on port 1: Switch 3 - <snip>
Neighbor on port 2: 0000.0000.0000
Switch 2:
Power budget: 2375
Power allocated: 919
Low port priority value: 21
High port priority value: 12
Switch priority value: 3
Port 1 status: Shut
Port 2 status: Connected
Neighbor on port 1: 0000.0000.0000
Neighbor on port 2: Switch 3 - <snip>
Switch 3:
Power budget: 2043
Power allocated: 342
Low port priority value: 23
High port priority value: 14
Switch priority value: 5
Port 1 status: Connected
Port 2 status: Connected
Neighbor on port 1: Switch 2 - <snip>
Neighbor on port 2: Switch 4 - <snip>
Power stack name: power-stack-1-1
Stack mode: Power sharing
Stack topology: Ring
Switch 5:
Power budget: 1964
Power allocated: 342
Low port priority value: 24
High port priority value: 15
Switch priority value: 6
Port 1 status: Not connected
Port 2 status: Connected
Neighbor on port 1: 0000.0000.0000
Neighbor on port 2: Switch 1 - <snip>
Switch 1:
Power budget: 2375
Power allocated: 851
Low port priority value: 20
High port priority value: 11
Switch priority value: 2
Port 1 status: Connected
Port 2 status: Not connected
Neighbor on port 1: Switch 5 - <snip>
Neighbor on port 2: 0000.0000.0000
Special Considerations
- Consult hardware installation guide for PoE budget available on each model. Some models have low PoE budget, such as C9300-48UXM that has a PoE budget of 490 W with 1100 WAC power supply, this can be misinterpreted as hardware failure.
- It has been seen some scenarios where a second power supply is inserted but PoE budget remains as budget from one single PS. When a switch does not detect PoE budget for a second PS and power supplies are detected on
Good
status, you can try to perform a full power cycle as workaround.
Remove the power cords from both PS to turn off the switch then:
- Remove PS1.
- Remove PS2.
- Wait couple minutes.
- Re-insert PS1
- Re-insert PS2
- Connect power cord to PS1
- Connect power cord to PS2.
Note: In case of a stack, all members affected need to be power cycled.
Catalyst 9500
Verification Commands
Use show power detail
privilege EXEC command to verify power supply status, you can also use this command to check power supply capacity and model.
Switch#show power detail
Switch:1
Power Fan States
Supply Model No Type Capacity Status 0 1
------ -------------------- ---- -------- --------- -----------
PS0 C9K-PWR-650WAC-R AC 650 W ok good N/A
PS1 Not Present N/A N/A N/A N/A N/A
Fan Fan States
Tray Status 0 1 2 3
------ ---------- -----------------------
FM0 ok good good good good
FM1 ok good good good good
Switch:2
<snip>
Use show platform hardware chassis power-supply detail switch [switch number] all
privilege EXEC command to verify input and output values are under proper ranges (This command also works for C9600 platform).
Switch#show platform hardware chassis power-supply detail switch 1 all
PS1:
Input Voltage : 200.0000 V
Output Voltage : 12.0480 V
Input Current : 0.6800 A
Output Current : 9.7500 A
Input Power : 131.0000 W
Output Power : 118.0000 W
Temperature 1 : 23.0000 C
Temperature 2 : 29.0000 C
Temperature 3 : 28.0000 C
Fan Speed 1 : 10176.0000 RPM
PS2:
<snip>
Note: Consult data sheet for power supply specifications.
Catalyst 9400 and 9600
Power Supplies Configuration Modes
Combined Mode
This is the default power supply mode. All available power supplies are active, those share power and can operate at up to 100 percent capacity. Available power in the combined mode is the sum of the individual power supplies.
If there is other power supply mode configured, you can use power redundancy-mode combined
command to return to default mode:
Switch(config)#power redundancy-mode switch 1 combined
Redundant Mode N+1
For this mode n number of power supply modules are active (n can be one to seven power supply modules) +1 is the power supply module reserved for redundancy.
The default standby power supply slot is PS8. Specify a standby slot with the power redundancy-mode redundant n+1 [standby-PS-slot]
command.
In the next example, power supply inserted in slot 5 is configured as standby:
Switch(config)#power redundancy-mode switch 1 redundant N+1 5
Redundant Mode N+N
For this mode n number of power supplies are active and n number of power supply modules are configured as standby. The default standby slots for this mode are PS5 through PS8. Specify the standby slots with the power redundancy-mode redundant n+n [standby-PS-slots]
command.
In the next example, power supplies inserted in slots 2, 3 and 4 are configured as standby:
Switch(config)#power redundancy-mode switch 1 redundant N+N 2 3 4
Verification Commands
Use show environment status
privilege EXEC command to verify power supply status, PS Current Configuration Mode
and PS Current Operating State
.
Switch#show environment status
Switch:1
Power Fan States
Supply Model No Type Capacity Status 1 2
------ -------------------- ---- -------- ------------ -----------
PS1 C9400-PWR-3200AC ac 3200 W active good good
PS2 C9400-PWR-3200AC ac 3200 W active good good
PS Current Configuration Mode : Combined
PS Current Operating State : Combined
Power supplies currently active : 2
Power supplies currently available : 2
<snip>
Switch 1:
Fantray : good
Power consumed by Fantray : 540 Watts
Fantray airflow direction : side-to-side
Fantray beacon LED: off
Fantray status LED: green
SYSTEM : GREEN
With show power detail
privilege EXEC command, you can also verify the amount of power consumed or reserved for each line card, supervisor and even for the Fan Tray. Additionally, you can verify the power budget mode, it can be either Single Sup
or Dual Sup
.
Switch#show power detail
Switch:1
Power Fan States
Supply Model No Type Capacity Status 1 2
------ -------------------- ---- -------- ------------ -----------
PS1 C9400-PWR-3200AC ac 3200 W active good good
PS2 C9400-PWR-3200AC ac 3200 W active good good
PS Current Configuration Mode : Combined
PS Current Operating State : Combined
Power supplies currently active : 2
Power supplies currently available : 2
Switch:2
<snip>
Switch:1
Power Summary Maximum
(in Watts) Used Available
------------- ------ ---------
System Power 1670 1670
Inline Power 0 4730
------------- ------ ---------
Total 1670 6400
Switch:2
<snip>
Switch:1
Automatic Linecard Shutdown : Enabled
Power Budget Mode : Dual Sup
autoLC Power Out of In
Mod Model No Priority State Budget Instantaneous Peak Reset Reset
--- -------------------- -------- -------- ------ ------------- ---- ------ -----
1 C9400-LC-24XS 0 accepted 200 94 96 200 10
2 C9400-LC-48U 1 accepted 65 32 33 65 5
3 C9400-SUP-1XL 0 accepted 400 239 252 400 130
4 C9400-SUP-1XL 0 --- 400 239 252 0 130
5 C9400-LC-48H 2 accepted 65 31 32 65 5
-- Fan Tray 0 accepted 540 -- -- 540 --
--- -------------------- -------- -------- ------ ------------- ---- ------ -----
Total 1670
Note: When power budget mode is Dual Sup
, it automatically reserves power for a second supervisor even when there is no second supervisor installed.
Special Considerations
ROMMON Variable SINGLE_SUP_CHASSIS
By default, the system reserves power for both supervisors to ensure high availability. Some C9600 can be configure with ROMMON variable SINGLE_SUP_CHASSIS=”0”
or SINGLE_SUP_CHASSIS=”1”
.
When this variable is set to 0 it indicates the power budget mode is for Dual Sup
, when it is set to 1 it indicates power budget mode is Single Sup
. You can verify if this variable is configured with show romvar
privilege EXEC command.
Switch#show romvar | in SUP
MODEL_NUM="C9600-SUP-1"
SINGLE_SUP_CHASSIS="0"
When ROMMON variable SINGLE_SUP_CHASSIS
is set to 1, it is not reflected in command show power detail
, it can still show power budget mode as Dual Sup
, however, the reserved power for a second supervisor reflects 0.
Power Budget Mode : Dual Sup
Power Out of In
Mod Model No State Budget Instantaneous Peak Reset Reset
--- -------------------- -------- ------ ------------- ---- ------ -----
1 C9600-LC-48YL accepted 230 0 0 230 10
2 C9600-LC-24C accepted 200 0 0 200 10
3 C9600-SUP-1 accepted 775 0 0 775 202
4 C9600-SUP-1 --- 0 -- -- 0 0
FM1 C9606-FAN accepted 450 -- -- 450 --
Although the ROMMON variable indicates single sup mode, when a second supervisor is inserted, that supervisor consumes the proper power budget if there is enough power available. If you need the switch to reserve power for second supervisor even when there is no second supervisor installed, you can set ROMMON variable SINGLE_SUP_CHASSIS
to 0, for this you need to enter to ROMMON mode.
Note: If you want to install a second supervisor, always remember to have the proper number of power supplies installed.
Power Budget Mode Dual Sup
When there is only one supervisor installed and there are not enough power supplies installed, the default power budget mode can trigger a scenario where the line cards are prevented to receive power and show power deny status.
Mod Model No State Budget Instantaneous Peak Reset Reset
--- -------------------- -------- ------ ------------- ---- ------ -----
1 C9600-LC-48YL denied 10 0 0 230 10
2 C9600-LC-24C denied 10 0 0 200 10
3 C9600-SUP-1 accepted 775 0 0 775 202
4 C9600-SUP-1 --- 775 -- -- 775 0
FM1 C9606-FAN accepted 450 -- -- 450 --
--- -------------------- -------- ------ ------------- ---- ------ -----
Total allocated power: 2020
Total required power: 2430
In order to solve this, you can configure the power budget mode for Single Sup
. This power budget mode allows the switch to use the reserved power for the second supervisor to enable the line cards.
Switch(config)#power budget mode single-sup
If you need to install a second supervisor in some point, remember to configure the switch back to Dual Sup
and to install the proper number of power supplies needed to meet the power requirements.
Switch(config)#no power budget mode single-sup
Warning: If you do not configure the switch back to power budget mode Dual Sup
and you do not install the proper number of PS, this can trigger a low power condition where the system can shut down.
Tip: Cisco Power Calculator is an educational resource that can help you as a starting point to plan you power requirements.